Skip to main content
ABB 2CDS271006R0165 — 1-Pole MCB (DIN Rail)

ABB 2CDS271006R0165 MCB, B-Curve, 16 A, 1-Pole, 10 kA

MPN2CDS271006R0165

ABB System pro M compact S200 series, miniature circuit breaker, B-curve, 16 A, 1-pole, 440 V, 10 kA Icn, 15 kA Icu, DIN rail mount, screw terminals, IP20/IP40.

Independent distributor — new & surplus sourcingAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

2CDS271006R0165 — Electrical & Protection
ParameterValue
Overvoltage categoryIII
2CDS271006R0165 — Mounting & Connection
ParameterValue
Width17.5 mm
Height88 mm
Depth69 mm
2CDS271006R0165 — Other specifications
ParameterValue
Poles1
IP ratingIP20;IP40
MountingDIN Rail Mount
Current16 A
Terminal contact typeScrew
Voltage440 V
Tripping characteristicsB
Tightening torque - Screw-Type max.2.8 Nm
Rated Short-Circuit breaking capacity icn10 kA
Rated Short-Circuit breaking capacity icu15 kA

Product details

The ABB 2CDS271006R0165 is a 1-pole miniature circuit breaker from the System pro M compact S200 series, rated 16 A with B-curve tripping characteristics. It fits a standard 17.5 mm DIN-rail slot — one module wide — and is sized for lighting, socket-outlet, and general-purpose protection in residential and light commercial distribution boards.

Breaking capacity and coordination

Rated short-circuit breaking capacity Icn is 10 kA per EN 60898, which is the standard for household and similar installations. The ultimate breaking capacity Icu is 15 kA per IEC 60947-2, covering industrial panel applications where the prospective fault current may be higher. For most distribution boards fed from a 100–200 kVA transformer, 10 kA is sufficient; the 15 kA Icu gives headroom for closer-coupled sub-distribution or higher-fault installations. Overvoltage category III means the MCB is rated for fixed installation downstream of the main distribution board — permanent connection, not plug-in. Rated insulation voltage 440 V covers 230/400 V three-phase systems with margin.

Mounting and enclosure fit

DIN-rail mount on a standard 35 mm top-hat rail. Width 17.5 mm, height 88 mm, depth 69 mm — one module, so it occupies a single 18 mm pitch in a distribution board. IP20 at the front terminals, IP40 for the enclosure body: suitable for dry indoor panels, not for washdown or outdoor exposure. Screw terminals accept up to 2.8 Nm tightening torque — typical for 2.5–4 mm² conductors.

Frequently asked questions

What is the breaking capacity of 2CDS271006R0165?

Rated short-circuit breaking capacity Icn is 10 kA per EN 60898, and ultimate breaking capacity Icu is 15 kA per IEC 60947-2.

What does the B-curve tripping characteristic mean?

B-curve means the MCB trips magnetically at 3–5 times rated current — 48–80 A for this 16 A unit. It is designed for resistive and lighting loads with low inrush; not recommended for motor or transformer circuits where C or D curves are needed.

Where can I buy 2CDS271006R0165?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

MPN
2CDS271006R0165