The 10 kA Icn (rated short-circuit breaking capacity per EN 60898) and 25 kA Icu (ultimate breaking capacity per IEC 60947-2) tell you this breaker can safely interrupt fault currents up to those levels at 440 V, which covers most commercial and light industrial panel applications. The 440 V rated insulation voltage (Ui) confirms it's rated for 400 V three-phase systems with margin.
Panel integration and deployment
Dimensions: 88 mm high, 35 mm wide per pole (so 70 mm wide for this 2-pole unit), 69 mm deep. The bi-directional cylinder-lift terminals accept up to 2.8 Nm tightening torque.