Skip to main content
ABB 2CDS272061R0065 — 2-Pole MCB (DIN Rail)

ABB 2CDS272061R0065 MCB, B Curve, 6 A, 2-Pole, 10 kA

MPN2CDS272061R0065

ABB, System pro M compact S200 series, miniature circuit breaker (MCB), B characteristic, 6 A, 2-pole, 440 V rated insulation voltage, 10 kA Icn / 25 kA Icu breaking capacity, DIN rail mount, IP20 / IP40.

$224.66 – $257.52Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

2CDS272061R0065 — Protection
ParameterValue
Overvoltage categoryIII
2CDS272061R0065 — Mechanical
ParameterValue
Width35 mm
Height88 mm
Depth69 mm
2CDS272061R0065 — Other specifications
ParameterValue
Poles2
IP ratingIP20;IP40
MountingDIN Rail Mount
Current6 A
Terminal contact typeBi-Directional Cylinder Lift
Voltage440 V
Tripping characteristicsB
Tightening torque - Screw-Type max.2.8 Nm
Rated Short-Circuit breaking capacity icn10 kA
Rated Short-Circuit breaking capacity icu25 kA

Product details

On a 440 V insulated system the 10 kA Icn service breaking capacity handles the fault level typical of most commercial and light industrial sub-distribution boards; the 25 kA Icu ultimate capacity gives additional headroom for coordination studies.

The 35 mm width occupies one standard modular position, and the 69 mm depth leaves clearance for wiring in a typical 120 mm deep enclosure. The IP20 finger-safe front face suits enclosed distribution boards; the IP40 rating on the terminals means the breaker is protected against solid objects over 1 mm — adequate for clean, dry panel environments. Terminal tightening torque is 2.8 Nm max, compatible with a standard Pozidriv No. 2 bit.

The bi-directional cylinder-lift terminal design accepts both copper and aluminium conductors and allows loop-through wiring without separate busbar connectors — a time-saver on multi-pole assemblies.

Frequently asked questions

What is the breaking capacity of 2CDS272061R0065?

The rated short-circuit breaking capacity Icn is 10 kA per IEC 60898, and the ultimate breaking capacity Icu is 25 kA per IEC 60947-2. The 10 kA figure governs the service duty for standard distribution; the 25 kA Icu is used for selectivity and coordination calculations.

Where can I buy 2CDS272061R0065 and get current pricing?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

What does the B tripping characteristic mean for this MCB?

The B curve trips magnetically at 3 to 5 times rated current (18 to 30 A for this 6 A breaker). It is the standard choice for resistive loads, lighting, and general-purpose circuits where inrush current is low — not for motor starting or transformer primary protection, where a C or D curve would be specified.

MPN
2CDS272061R0065