K-curve 4 A MCB for inductive and motor-starting protection
The K curve is designed for inductive loads — it tolerates the higher inrush currents of motors, transformers, and solenoid valves without nuisance tripping, while still providing short-circuit protection. Rated insulation voltage is 440 V, with a short-circuit breaking capacity of 11.2 kA per IEC/EN 60898 (Icn) and 15 kA per IEC/EN 60947-2 (Icu).
The 2-pole body occupies two modular 17.5 mm width units (35 mm total width), with a depth of 69 mm and height of 111 mm.