Skip to main content
ABB 3ABD0000137242 — AC Drive (VFD) 240V

ABB 3ABD0000137242 ACS880-01 Drive, 37 kW, 145 A

MPN3ABD0000137242
Active

ABB ACS880-01 series, wall-mounted single drive, 3ABD0000137242, 200–240 V 3-phase input, 37 kW normal-use / 145 A, frame size R6, IP21, NEMA 1.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3ABD0000137242 — Electrical Output
ParameterValue
Output power, normal duty (Pn)37 kW
Output current, normal duty (In)145 A
Output power, heavy duty (PhD)30.0 kW
Output current, heavy duty (IhD)105 A
Output power, light-overload duty (PlD)37 kW
Output current, light-overload duty (IlD)138 A
3ABD0000137242 — Electrical Input
ParameterValue
Input voltage range200 ... 240 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3ABD0000137242 — Mechanical
ParameterValue
Degree of protection (IP)IP21
Enclosure type (NEMA)Type1
Frame sizeR6
Mounting typeWall-mounted

Product details

Drive selection memo — 3ABD0000137242

The ABB 3ABD0000137242 is an ACS880-01-145A-2 wall-mounted single drive rated for 200–240 V 3-phase input. Normal-use output is 37 kW at 145 A; heavy-duty use drops to 30 kW at 105 A.

Frame size R6 tells you the mechanical envelope — bolt-hole pattern, duct clearance, and replacement footprint. If you're swapping an existing R6 drive, this unit slides into the same wall-mount holes without re-drilling the backplate. IP21 and NEMA Type 1 mean the drive is built for clean indoor environments — no washdown, no dust, no condensation. If the panel sees coolant mist or humidity, you'll need a higher IP enclosure around it.

Installation note

Wall-mounted design means the drive arrives with its own enclosure — no separate cabinet build for the power stage. Mounting on a solid vertical surface with the gland plate facing down keeps cable entry clean. The R6 frame is heavy; plan for two-person lift or a mechanical hoist during installation.

Frequently asked questions

What is the frame size of this drive?

Frame size R6, which defines the mounting footprint and enclosure dimensions for the ACS880-01 series.

What are the normal-use and heavy-duty output ratings?

Normal-use: 37 kW at 145 A. Heavy-duty: 30 kW at 105 A. Light-overload: 37 kW at 138 A.

What enclosure protection does it have?

IP21 and NEMA Type 1 — suitable for clean, dry indoor installations only.

MPN
3ABD0000137242