Skip to main content
ABB 3ABD00027042-D — AC Drive (VFD) 480V

ABB 3ABD00027042-D ACS510 Drive, 160 kW, 290 A, IP54

MPN3ABD00027042-D
Active

ABB ACS510 series, frame size R6, 160 kW output power, 290 A output current, IP54, NEMA Type12, 380-500 V input, 3-phase.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3ABD00027042-D — Power & Output
ParameterValue
Output power, normal duty160 kW
Output current, normal duty290 A
Apparent power output201 kV·A
Efficiency class (IE)IE2
Standby power loss41 W
3ABD00027042-D — Input / Supply
ParameterValue
Input voltage range380 ... 500 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3ABD00027042-D — Mechanical & Cooling
ParameterValue
Frame sizeR6
NEMA enclosure typeType12
Degree of protection (IP)IP54
Mounting typeModule
3ABD00027042-D — Environmental
ParameterValue
Temperature rating (max.)40 °C

Product details

The ABB 3ABD00027042-D is an ACS510-01-290A-4+B055 variable-frequency drive delivering 160 kW output power at 290 A continuous current, sized for a 3-phase induction motor on a 380-500 V supply. The IP54 / NEMA Type12 enclosure suits it for floor-mounting in industrial environments where dust and splash are present — pump, fan, or conveyor duty inside a non-conditioned plant area. Standby loss of 41 W is the heat the drive dissipates when the motor is stopped but the DC bus remains charged; factor that into panel ventilation if the drive sits idle for extended periods.

Efficiency and operating range

Rated IE2 efficiency class, which meets the minimum for most industrial applications in regions where IE3 is not mandated for this power band. The 40 °C ambient rating is the standard maximum for continuous full-load operation; above that, output current must be de-rated per the drive's thermal curve — a consideration if the drive is mounted in a confined space with other heat sources.

Frequently asked questions

What is the frame size of 3ABD00027042-D?

The drive is built on frame size R6, which corresponds to the mechanical dimensions and mounting footprint for the 160 kW / 290 A rating in the ACS510 platform.

What is the standby loss of this drive?

Standby loss is 41 W. This is the power the drive consumes when the motor is stopped but the DC bus remains energized — relevant for panel heat-load calculations.

Where can I buy 3ABD00027042-D?

This drive is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
3ABD00027042-D