What this drive module is and what it delivers
It runs on a 380-480 V, 3-phase supply and is rated for a frequency range of 47.5 to 63 Hz. The module is built in frame size R10, with an IP00 open-type enclosure — meaning it's designed for cabinet installation, not standalone floor placement.
Duty ratings that matter for your load profile
This drive carries three distinct output ratings depending on the duty cycle. Normal use (Pn) is 250 kW at 505 A; heavy-duty use (PhD) drops to 200 kW at 361 A; light-overload use (PlD) stays at 250 kW but at a slightly lower 485 A. The normal-use rating suits variable-torque applications like pumps and fans.
Efficiency and enclosure
Rated IE2 efficiency, which meets the minimum for most industrial installations. The IP00 enclosure means no built-in protection against dust or moisture — it relies on the cabinet's own IP rating. The NEMA Open Type designation confirms the same: it's a chassis-style module for integration into a larger panel.