The 3ABD00039240-D: Three duty points are listed: normal use (45 kW, 49 A), heavy-duty (37 kW, 42 A), and light-overload (45 kW, 47 A). The heavy-duty figure governs continuous operation under high starting torque or cyclic loads — sizing a motor at 37 kW leaves headroom for the drive. Light-overload matches normal-use power but at slightly lower current, reflecting a different thermal profile. Frame size R5 accommodates the power stage and heatsink for these ratings.
Wall-mounted unit, NEMA Type 1 for indoor use with IP21 ingress protection. WEEE category 4 (large equipment, any external dimension >50 cm). No DIN-rail option — panel or backplate mounting with gland-plate entry for cables.