Skip to main content
ABB 3ABD00039472-D — AC Drive (VFD) 600V

ABB 3ABD00039472-D ACS880-04 Drive Module, 400 kW, 430 A

MPN3ABD00039472-D
Active

ABB ACS880-04 industrial single drive module, 3-phase, 525-690 V input, 400 kW / 430 A normal use, IP20, R10 frame.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3ABD00039472-D — Identification
ParameterValue
Frame sizeR10
3ABD00039472-D — Electrical (input)
ParameterValue
Input voltage range525 ... 690 V
Number of phases3-phase
Frequency range47.5 ... 63 Hz
3ABD00039472-D — Output / Performance
ParameterValue
Output power, normal duty400 kW
Output power, heavy duty350 kW
Output power, light overload450 kW
Output current, normal duty430 A
Output current, heavy duty360 A
Output current, light overload420 A
3ABD00039472-D — Mechanical
ParameterValue
Mounting typeModule
NEMA enclosure typeOpen Type
3ABD00039472-D — Environmental
ParameterValue
Degree of protection (IEC, IP)IP20

Product details

The 3ABD00039472-D is an ABB ACS880-04 LV AC industrial single drive module, rated for 3-phase 525-690 V input with a frequency range of 47.5 to 63 Hz. It delivers 400 kW normal-use output at 430 A, with heavy-duty capability of 350 kW at 360 A and light-overload rating of 450 kW at 420 A. The R10 frame size and IP20 enclosure suit cabinet-mount installations where the drive is protected from direct contact but not from dust ingress.

The three duty ratings matter for motor sizing: normal-use 430 A covers a standard 400 kW induction motor on a pump or fan; heavy-duty 360 A handles a 350 kW motor with constant-torque loads like conveyors; light-overload 420 A suits a 450 kW motor with low starting torque. The 525-690 V input range matches 600 V and 690 V industrial grids common in heavy process plants.

Installation notes

Mount as a module in a cabinet with adequate ventilation — the IP20 rating means no protection against water or dust ingress, so keep it in a clean, dry enclosure. The R10 frame size dictates the physical footprint and bus-bar layout; verify cabinet depth and cooling airflow before committing the panel layout.

Frequently asked questions

What is the frame size of this drive module?

The frame size is R10, which determines the mounting footprint and bus-bar connections for cabinet integration.

What are the output ratings for different duty types?

Normal use: 400 kW / 430 A; heavy-duty use: 350 kW / 360 A; light-overload use: 450 kW / 420 A. These allow matching to motor load profiles.

MPN
3ABD00039472-D