Skip to main content
ABB 3ABD00039481-D — AC Drive (VFD) 600V

ABB 3ABD00039481-D ACS880-04 Drive Module, 500 kW, 522 A, Fr

MPN3ABD00039481-D
Active

ABB ACS880-04 LV AC single drive module, 3ABD00039481-D, frame R11, 500 kW / 522 A normal use, 525–690 V input, IP20, active.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3ABD00039481-D — Identification
ParameterValue
Frame sizeR11

Electrical (input)

3ABD00039481-D — Electrical (input)
ParameterValue
Input voltage range525 ... 690 V
Number of phases3-phase
Frequency range47.5 ... 63 Hz

Output / Performance

3ABD00039481-D — Output / Performance
ParameterValue
Output power, normal duty500 kW
Output power, heavy duty450 kW
Output power, light overload500 kW
Output current, normal duty522 A
Output current, heavy duty455 A
Output current, light overload505 A
Efficiency level (IE class)IE2

Mechanical

3ABD00039481-D — Mechanical
ParameterValue
Mounting typeModule
NEMA enclosure typeOpen Type

Environmental

3ABD00039481-D — Environmental
ParameterValue
Degree of protection (IEC, IP)IP20

Product details

What this drive module is and what it delivers

The ABB 3ABD00039481-D is an LV AC industrial single drive module rated for 500 kW normal-use output at 522 A, with a 525–690 V three-phase input. Frame size R11, IP20 enclosure, open type.

The rating that decides the fit

Normal-use output is 500 kW at 522 A, but the heavy-duty rating drops to 450 kW at 455 A. If your application is a pump or fan with variable torque, the light-overload rating holds at 500 kW / 505 A. Match the duty cycle, not the headline number.

Frequently asked questions

What is the frame size of 3ABD00039481-D?

Frame size R11. This determines the physical mounting footprint and bus-bar layout for the drive cabinet.

What input voltage and frequency does this module accept?

Three-phase 525–690 V input, 47.5–63 Hz. Common for 690 V industrial networks in mining, marine, and large pumping installations.

What is the difference between the normal-use and heavy-duty ratings?

Normal use is 500 kW / 522 A; heavy-duty drops to 450 kW / 455 A. The heavy-duty figure applies when the motor demands constant torque across the speed range — conveyors, extruders, positive-displacement pumps. Light-overload (variable-torque) stays at 500 kW / 505 A.

MPN