Skip to main content
ABB 3ABD00039520-D — AC Drive (VFD) 600V

ABB 3ABD00039520-D ACS880-04 Drive Module, 500 kW, 522 A

MPN3ABD00039520-D
Active

ABB ACS880-04 LV AC industrial single drive module, 3ABD00039520-D, R11 frame, 500 kW / 522 A normal use, 525-690 V input, IP20, 3-phase.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3ABD00039520-D — Identification
ParameterValue
Frame sizeR11
3ABD00039520-D — Electrical (input)
ParameterValue
Input voltage range525 ... 690 V
Number of phases3-phase
Frequency range47.5 ... 63 Hz
3ABD00039520-D — Output / Performance
ParameterValue
Output power, normal duty500 kW
Output power, heavy duty450 kW
Output power, light overload500 kW
Output current, normal duty522 A
Output current, heavy duty455 A
Output current, light overload505 A
3ABD00039520-D — Mechanical
ParameterValue
Mounting typeModule
NEMA enclosure typeOpen Type
3ABD00039520-D — Environmental
ParameterValue
Degree of protection (IEC, IP)IP20

Product details

Drive module for 500 kW motor loads on 525-690 V line

The 3ABD00039520-D is an ABB ACS880-04 LV AC industrial single drive module rated for 500 kW normal-use output at 522 A, with heavy-duty capability at 450 kW / 455 A. Input voltage spans 525 to 690 V three-phase, frequency range 47.5 to 63 Hz. The R11 frame size and IP20 enclosure suit cabinet-mounted installations where the drive is part of a larger panel assembly.

Three output current ratings define the load envelope: 522 A normal use (In), 505 A light-overload (IlD), and 455 A heavy-duty (IhD). Normal-use power is 500 kW; heavy-duty drops to 450 kW. For a continuous conveyor or pump at 500 kW the normal-use rating applies. If the load profile includes short overload peaks — crushers, hoists — the heavy-duty 455 A figure governs the thermal limit. Light-overload use at 505 A covers applications with moderate transient demands.

R11 frame mounts as a module within a drive cabinet; the IP20 rating means it requires enclosure protection from dust and tools. Input voltage range covers 525-690 V, common for 600 V and 690 V industrial grids in mining, marine, and heavy process lines. The 47.5-63 Hz frequency acceptance handles 50 Hz and 60 Hz supplies without derating.

Frequently asked questions

What is the frame size of this drive module?

The frame size is R11, which determines the physical mounting footprint and bus-bar connections within the cabinet.

What are the normal-use and heavy-duty output ratings?

Normal use: 500 kW at 522 A. Heavy-duty: 450 kW at 455 A. Light-overload: 500 kW at 505 A.