Skip to main content
ABB 3ABD00039525-D — AC Drive (VFD) 600V

ABB 3ABD00039525-D ACS880 Drive Module, 630 kW, 650 A

MPN3ABD00039525-D
Active

ABB ACS880 LV AC single drive module, 3ABD00039525-D, 630 kW / 650 A normal use, 525-690 V input, frame R11, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3ABD00039525-D — Identification
ParameterValue
Frame sizeR11
3ABD00039525-D — Electrical (input)
ParameterValue
Input voltage range525 ... 690 V
Number of phases3-phase
Frequency range47.5 ... 63 Hz
3ABD00039525-D — Output / Performance
ParameterValue
Output power, normal duty630 kW
Output power, heavy duty560 kW
Output power, light overload630 kW
Output current, normal duty650 A
Output current, heavy duty571 A
Output current, light overload630 A
3ABD00039525-D — Mechanical
ParameterValue
Mounting typeModule
NEMA enclosure typeOpen Type
3ABD00039525-D — Environmental
ParameterValue
Degree of protection (IEC, IP)IP20

Product details

The ABB 3ABD00039525-D is an LV AC industrial single drive module from the ACS880 family, rated 630 kW normal-use output at 650 A (IEC) on a 525-690 V three-phase supply. Heavy-duty use drops to 560 kW / 571 A; light-overload use holds 630 kW at 630 A. Frame size R11, IP20 open-type enclosure. Frequency range 47.5-63 Hz covers 50/60 Hz mains.

Lifecycle status is active per ABB's current product stage. This module is a standard catalog item, not a phase-out or last-time-buy.

The 650 A normal-use output is the figure to size branch protection and cabling for continuous motor duty. Heavy-duty 571 A is the limiting number for high-start-torque or cyclic loads — that 79 A delta matters when the application calls for a 560 kW motor on a crusher or conveyor. Input voltage 525-690 V suits 690 V industrial grids common in European and marine installations; 525 V minimum means it won't work on a standard 400 V supply without a step-up transformer.

Integration notes

Mounts as a module — frame R11 dictates panel cutout and busbar layout. IP20 open type requires enclosure for dust and touch protection. Three-phase input; frequency tolerance 47.5-63 Hz covers weak-grid or genset feeds. WEEE category 4 (large equipment >50 cm) applies for end-of-life handling in EU.

Frequently asked questions

What is the frame size of this drive module?

Frame size R11. This determines physical mounting dimensions and busbar connections.

What are the normal-use and heavy-duty output ratings?

Normal use: 630 kW / 650 A. Heavy-duty use: 560 kW / 571 A. Light-overload use: 630 kW / 630 A.

MPN