It delivers 630 kW normal-use output at 650 A, with heavy-duty capability at 560 kW / 571 A, on a 525-690 V three-phase supply. Efficiency is rated IE2.
The 650 A normal-use current (In) and 630 kW power (Pn) define the standard operating point for continuous motor loads. For applications with higher peak demands or shorter duty cycles, the heavy-duty curve drops to 571 A / 560 kW — that's the number to size against if your load profile includes sustained overloads. The light-overload rating matches the normal-use power but at 630 A, so the headroom is in current, not power. Input voltage range is 525-690 V, 47.5-63 Hz, three-phase. The module is open-type (NEMA), IP20, so it needs a cabinet. Frame R11 determines the mechanical footprint and bus-bar interface — verify panel cutout and mounting rail compatibility before committing the BOM line.