What this module delivers
It takes a 525...690 V three-phase input and delivers 630 kW / 650 A under normal use (light-overload: 630 kW / 630 A; heavy-duty: 560 kW / 571 A). IP20 enclosure, open type.
The normal-use 650 A output is the number to size buswork and fusing for. If your application cycles heavy loads — say a crusher or centrifuge — the heavy-duty rating of 571 A is the one that governs thermal capacity. Light-overload (630 A,) covers pumps and fans with low starting torque. Frequency range 47.5...63 Hz covers 50 and 60 Hz grids globally.
Physical integration
R11 frame, IP20, open type. Mounts as a module in a multi-drive lineup — needs cabinet ventilation, not standalone. No gland plate or conduit entry on the module itself; terminations are busbars and cable lugs inside the enclosure.