Normal-use output is 710 kW and 721 A, with heavy-duty use rated at 560 kW and 571 A — that's the number you size by for constant-torque loads like conveyors or extruders. Light-overload use (typically for pumps and fans) comes in at 630 kW and 705 A. Frame size R11, IP20, open type — this is a cabinet-mount module, not a standalone enclosure.
R11 frame, IP20, open type — plan for cabinet installation with proper ventilation. Input frequency range 47.5-63 Hz covers 50 and 60 Hz grids. The module is sized for a 710 kW motor on normal duty; derate the output current if ambient temperature exceeds the drive's rated range or if installation altitude goes above 1000 m. WEEE category 4 (Large Equipment) applies for end-of-life handling.