Skip to main content
ABB 3ABD00039571-D — AC Drive (VFD) 600V

ABB 3ABD00039571-D ACS880-04 Drive Module, 710 kW, 721 A

MPN3ABD00039571-D
Active

ABB ACS880-04 single drive module, 3ABD00039571-D, 710 kW normal duty, 721 A output, 525-690 V input, IP20, frame R11.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3ABD00039571-D — Identification
ParameterValue
Frame sizeR11
3ABD00039571-D — Electrical (input)
ParameterValue
Input voltage range525 ... 690 V
Number of phases3-phase
Frequency range47.5 ... 63 Hz
3ABD00039571-D — Output / Performance
ParameterValue
Output power, normal duty710 kW
Output power, heavy duty560 kW
Output power, light overload630 kW
Output current, normal duty721 A
Output current, heavy duty571 A
Output current, light overload705 A
Efficiency level (IE class)IE2
3ABD00039571-D — Mechanical
ParameterValue
Mounting typeModule
NEMA enclosure typeOpen Type
3ABD00039571-D — Environmental
ParameterValue
Degree of protection (IEC, IP)IP20

Product details

Drive module for high-power 3-phase motor control

Normal-duty output is rated 710 kW at 721 A, with heavy-duty use at 560 kW and 571 A, and light-overload use at 630 kW and 705 A.

Three output ratings let you match the drive to the application profile. Heavy-duty (PhD 560 kW, IhD 571 A) provides headroom for high-starting-torque or shock-load applications such as crushers or extruders. Light-overload (PlD 630 kW, IlD 705 A) suits variable-torque loads like fans or centrifugal pumps where peak demand is intermittent. The frame size R11 houses the power stage for these current levels.

Frequently asked questions

What is the frame size of this drive module?

The frame size is R11.

What are the key output ratings?

Normal-duty output is 710 kW at 721 A; heavy-duty is 560 kW at 571 A; light-overload is 630 kW at 705 A.

What input voltage and frequency does it accept?

Input voltage is 525 to 690 V, frequency 47.5 to 63 Hz.

MPN
3ABD00039571-D