Output ratings and duty selection
The 3ABD00045154: Three duty ratings are listed: normal use at 7.5 kW / 17 A, heavy-duty use at 5.5 kW / 12.6 A, and light-overload use at 7.5 kW / 16.2 A. The heavy-duty figure governs continuous motor load in constant-torque applications; the light-overload figure applies where the load profile allows a higher sustained current at reduced torque margin.
Supply and protection
Input voltage range is 380-480 V, three-phase, with a frequency tolerance of 47.5-63 Hz. The enclosure is rated IP20 (open type per NEMA), suitable for installation inside a panel with additional environmental protection.
Product status is active. This is not a phase-out or NRND part; it is a current catalog item.