Skip to main content
ABB 3ABD00045185 — AC Drive (VFD) 480V

ABB 3ABD00045185 ACS380 drive module, 7.5 kW, 17 A, IP20

MPN3ABD00045185
Active

ABB ACS380 machinery drive module, 3ABD00045185, 7.5 kW normal-use output, 17 A, 380-480 V 3-phase, IP20, frame size R3, IE2.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3ABD00045185 — Power & Output
ParameterValue
Output power, normal duty7.5 kW
Output current, normal duty17 A
Output power, heavy duty5.5 kW
Output current, heavy duty12.6 A
Output power, light overload7.5 kW
Output current, light overload16.2 A
Efficiency class (IE)IE2
3ABD00045185 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3ABD00045185 — Mechanical & Cooling
ParameterValue
Frame sizeR3
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule

Product details

The ABB 3ABD00045185 is an ACS380 series LV AC machinery drive module in frame size R3. It delivers 7.5 kW normal-use output at 17 A (IEC) from a 380-480 V three-phase supply, with a heavy-duty rating of 5.5 kW / 12.6 A for constant-torque loads like conveyors or extruders. Light-overload use is rated at 7.5 kW / 16.2 A. The drive is IP20 open-type, intended for cabinet mounting.

The normal-use output (Pn 7.5 kW, In 17 A) is the rating for typical variable-torque fan/pump applications. For constant-torque or high-starting-torque loads, use the heavy-duty figure (PhD 5.5 kW, IhD 12.6 A) — that is the rating that governs motor sizing for conveyors, crushers, or positive-displacement pumps. The light-overload rating (PlD 7.5 kW, IlD 16.2 A) sits between the two, for applications with moderate overload cycles. Frame size R3 determines physical footprint and mounting hole pattern; verify cabinet depth and DIN-rail compatibility before panel layout.

Frequently asked questions

What is the frame size of this drive?

Frame size R3.

What input voltage and frequency does it accept?

380-480 V three-phase, 47.5-63 Hz.

What are the output ratings for normal and heavy duty?

Normal use: 7.5 kW / 17 A. Heavy duty: 5.5 kW / 12.6 A. Light overload: 7.5 kW / 16.2 A.

MPN
3ABD00045185