Specifications

Power & Output

3ABD00045414-D — Power & Output
ParameterValue
Output power, normal duty55 kW
Output current, normal duty106 A
Output power, heavy duty45 kW
Output current, heavy duty87 A
Output power, light overload55 kW
Output current, light overload100 A
Efficiency class (IE)IE2

Input / Supply

3ABD00045414-D — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Mechanical & Cooling

3ABD00045414-D — Mechanical & Cooling
ParameterValue
Frame sizeR5
NEMA enclosure typeType1
Degree of protection (IP)IP21
Mounting typeWall-mounted

Product details

The ABB 3ABD00045414-D is an LV AC wall-mounted drive for HVAC, rated 55 kW normal-use output at 106 A on a 380–480 V three-phase supply. Heavy-duty use drops to 45 kW at 87 A; light-overload use holds 55 kW at 100 A. Frame size R5, IP21 enclosure, IE2 efficiency.

Normal-use (Pn 55 kW, In 106 A) covers constant-torque HVAC fans and pumps at full speed. Heavy-duty (PhD 45 kW, IhD 87 A) handles variable-torque loads like compressors or conveyors where peak current is higher. Light-overload (PlD 55 kW, IlD 100 A) suits cyclic loads with moderate overloads. Match your motor's full-load amps to the appropriate column — oversizing to normal-use when the load is actually heavy-duty risks nuisance tripping.

Wall-mounted, IP21, NEMA Type 1 — suitable for indoor, non-condensing environments. Frame R5 means a specific footprint and gland-plate layout; verify panel cut-out dimensions against the installation manual before committing the backplate.

Frequently asked questions

What are the key output ratings for this drive?

Normal-use output is 55 kW at 106 A; heavy-duty output is 45 kW at 87 A; light-overload output is 55 kW at 100 A.

What is the frame size and enclosure type?

Frame size R5, IP21, NEMA Type 1, wall-mounted.

What input voltage and frequency does it accept?

380–480 V three-phase, 47.5–63 Hz.

MPN