Skip to main content
ABB 3ABD00045425-D — AC Drive (VFD) 480V

3ABD00045425-D ABB ACQ580-01-106A-4 55 kW Drive, 106 A, IP21

MPN3ABD00045425-D
Active

ABB ACQ580-01-106A-4 LV AC wall-mounted drive, 55 kW / 106 A normal use, 380-480 V, IP21, NEMA Type 1, Frame R5.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Power & Output

3ABD00045425-D — Power & Output
ParameterValue
Output power, normal duty55 kW
Output current, normal duty106 A
Output power, heavy duty45 kW
Output current, heavy duty87 A
Output power, light overload55 kW
Output current, light overload100 A
Efficiency class (IE)IE2

Input / Supply

3ABD00045425-D — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Mechanical & Cooling

3ABD00045425-D — Mechanical & Cooling
ParameterValue
Frame sizeR5
NEMA enclosure typeType1
Degree of protection (IP)IP21
Mounting typeWall-mounted

Product details

The ABB 3ABD00045425-D is a Frame R5 wall-mounted LV AC drive from the ACQ580 series, built for water and wastewater applications. It delivers 55 kW normal-use output at 106 A on a 380-480 V three-phase supply, with a heavy-duty rating of 45 kW at 87 A for tougher loads. The IP21 enclosure and NEMA Type 1 rating suit indoor panel mounting where dust and drip protection are needed.

The normal-use current of 106 A is the figure to size cables and upstream protection for continuous motor duty. If the application involves frequent starts or high breakaway torque, the heavy-duty curve at 87 A is the binding limit — oversizing one frame may be cheaper than nuisance trips. The IE2 efficiency level is the baseline for the drive itself; motor efficiency is separate. Input frequency tolerance from 47.5 to 63 Hz means the drive handles both 50 Hz and 60 Hz grids without derating. The 380-480 V input range covers standard European and North American line voltages within a single unit.

Wall-mounted Frame R5 — verify the gland plate area and cable bend radius against the panel depth before layout. IP21 allows top-entry conduits; NEMA Type 1 means no additional drip shield needed indoors. The drive is three-phase input only; single-phase supply requires an external step-up or phase converter.

Frequently asked questions

What is the frame size of this drive?

The frame size is R5, which is a wall-mounted enclosure for the ACQ580 series.

What are the normal-use and heavy-duty output ratings?

Normal use: 55 kW at 106 A. Heavy-duty use: 45 kW at 87 A. There is also a light-overload rating of 55 kW at 100 A.

MPN
3ABD00045425-D