Skip to main content
ABB 3ABD00045439-D — AC Drive (VFD) 480V

ABB 3ABD00045439-D ACS580-01-206A-4 Drive, 110 kW, 206 A

MPN3ABD00045439-D
Active

ABB ACS580-01 general purpose wall-mounted drive, 3-phase, 380–480 V, 110 kW / 206 A normal duty, IP21, IE2, frame R7.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Power & Output

3ABD00045439-D — Power & Output
ParameterValue
Output power, normal duty110 kW
Output current, normal duty206 A
Output power, heavy duty90 kW
Output current, heavy duty169 A
Output power, light overload110 kW
Output current, light overload196 A
Efficiency class (IE)IE2

Input / Supply

3ABD00045439-D — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Mechanical & Cooling

3ABD00045439-D — Mechanical & Cooling
ParameterValue
Frame sizeR7
NEMA enclosure typeType1
Degree of protection (IP)IP21
Mounting typeWall-mounted

Product details

For constant-torque or high-starting-torque applications, the heavy-duty rating of 169 A (90 kW) applies — that is the number to use when sizing for conveyors or extruders. A light-overload rating is also listed at 196 A (110 kW), which sits between the two. The IE2 efficiency class means the drive meets the minimum efficiency level required in most industrial installations today.

Physical and environmental specs

The drive is housed in frame size R7 and is wall-mounted. The enclosure is NEMA Type 1 with an IP21 ingress protection rating — suitable for indoor installation where dripping water and limited dust ingress are not a concern. It falls under WEEE Category 4 (Large Equipment), which affects end-of-life handling in EU jurisdictions.

Frequently asked questions

What is the frame size of this drive?

The drive has frame size R7.

What input voltage and frequency does it accept?

It accepts 380–480 V three-phase at 47.5–63 Hz.

What are the normal-use and heavy-duty current ratings?

Normal-use output current is 206 A (110 kW); heavy-duty output is 169 A (90 kW).

What is the enclosure type and protection rating?

The enclosure is NEMA Type 1 with IP21 protection.

MPN
3ABD00045439-D