Rating breakdown
The 3ABD00045703-D: Normal-use output (Pn 55 kW, In 106 A) covers constant-torque fan and pump loads at full speed. Heavy-duty rating (45 kW, 87 A) applies for higher starting torque or cyclic overload profiles — the drive's thermal model adjusts the current limit accordingly. Light-overload use (55 kW, 100 A) sits between the two, matching variable-torque centrifugal loads where peak demand is brief.
Wall-mounted, frame R5. No gland plate dimensions in this record, but the Type 12 conduit knockouts are standard for the frame. Verify cable entry size against the panel layout before cutting the backplate.