Skip to main content
ABB 3ABD00045773-D — AC Drive (VFD) 480V

ABB 3ABD00045773-D ACS580-04 Drive Module, 250 kW, 505 A

MPN3ABD00045773-D
Active

ABB, ACS580-04 series, LV AC general purpose drive module, 3ABD00045773-D, 250 kW normal-use, 505 A output, 380-480 V 3-phase input, frame R10, IP00.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Power & Output

3ABD00045773-D — Power & Output
ParameterValue
Output power, normal duty250 kW
Output current, normal duty505 A
Output power, heavy duty200 kW
Output current, heavy duty361 A
Output power, light overload250 kW
Output current, light overload485 A
Efficiency class (IE)IE2

Input / Supply

3ABD00045773-D — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Mechanical & Cooling

3ABD00045773-D — Mechanical & Cooling
ParameterValue
Frame sizeR10
NEMA enclosure typeOpen Type
Degree of protection (IP)IP00
Mounting typeModule

Product details

Drive module for 250 kW motor loads

The ABB 3ABD00045773-D is an active-production LV AC general purpose drive module rated for 250 kW normal-use output at 505 A and 380-480 V three-phase input. Frame size R10, IP00 open type — this is a chassis module intended for panel integration, not standalone floor mounting.

Three duty ratings are listed: normal-use (Pn 250 kW, In 505 A), heavy-duty (PhD 200 kW, IhD 361 A), and light-overload (PlD 250 kW, IlD 485 A). The heavy-duty figure governs continuous operation on a constant-torque load like a conveyor or extruder; the normal-use rating applies to variable-torque loads such as centrifugal pumps and fans. The light-overload current sits between the two — useful for applications with occasional peak demand but not sustained high torque.

Physical and electrical fit

Frame R10 defines the mechanical footprint and bus-bar layout — verify panel cutout and mounting rail compatibility with the installation manual. Input accepts 380-480 V at 47.5-63 Hz, three-phase. IP00 means no built-in protection against dust or water ingress; the enclosure must provide the required IP rating. Efficiency class IE2 is standard for this generation.

Frequently asked questions

What is the frame size of this drive module?

Frame size R10, which governs the physical dimensions and bus-bar layout for panel integration.

What input voltage and frequency does it accept?

380-480 V three-phase, 47.5-63 Hz.

What are the normal-use and heavy-duty power ratings?

Normal-use: 250 kW, 505 A. Heavy-duty: 200 kW, 361 A. Light-overload: 250 kW, 485 A.