ABB 3ABD00046036-D — AC Drives (VFD)

ABB 3ABD00046036-D ACQ580-01 Drive, 30 kW, 62 A, R4 Frame

MPN3ABD00046036-D
Active

ABB ACQ580-01 series, LV AC wall-mounted drive, 30 kW normal-use output, 62 A, R4 frame, IP21, IE2 efficiency, 380-500 V 3-phase input.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical

3ABD00046036-D — Electrical
ParameterValue
Input voltage380 ... 500 V
Frequency47.5 ... 63 Hz
Number of phases3-phase

Power & Current

3ABD00046036-D — Power & Current
ParameterValue
Output power, normal duty30 kW
Output power, heavy duty22 kW
Output power, light-overload duty30 kW
Output current, heavy duty44.6 A
Output current, normal duty62 A
Output current, light-overload duty58 A
Efficiency class (IE)IE2

Protection & Environmental

3ABD00046036-D — Protection & Environmental
ParameterValue
Degree of protection (IP)IP21
NEMA enclosure typeType1

Mechanical

3ABD00046036-D — Mechanical
ParameterValue
Frame sizeR4
Mounting typeWall-mounted

Product details

Drive selection memo — ACQ580-01, 30 kW

The ABB 3ABD00046036-D is an ACQ580-01 wall-mounted drive rated 30 kW normal use (62 A) on 380-500 V three-phase input. The R4 frame carries the IP21 sheet-steel enclosure for indoor panel or wall mounting. Heavy-duty duty cycle drops to 22 kW / 44.6 A — sized for pump and fan loads in water and wastewater service where the overload profile is well below the normal-use curve.

The heavy-duty rating (22 kW, 44.6 A) applies when the drive must deliver 150% overload for 60 seconds, typical for screw pumps, positive-displacement blowers, or lift stations with high breakaway torque. Light-overload use (30 kW, 58 A) sits between the two — a lower current limit than normal use despite the same power figure, meaning the drive's thermal capacity is the constraint, not the motor rating.

The R4 frame is sized for the 30 kW output stage — gland plate entry on the bottom, cable clearance for 3-phase power and control wiring. No DIN-rail option; the drive bolts directly to a backplate or wall bracket.

Frequently asked questions

What is the frame size of 3ABD00046036-D?

R4 frame size, wall-mounted with a NEMA Type 1 (IP21) enclosure.

What are the heavy-duty and normal-use ratings for this drive?

Normal use: 30 kW, 62 A. Heavy-duty use: 22 kW, 44.6 A. Light-overload use: 30 kW, 58 A.

Where can I buy 3ABD00046036-D and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no online stock or price is published for this industrial drive.

MPN
3ABD00046036-D