ABB 3ABD00046044-D — Inverter / VFD

ABB 3ABD00046044-D ACQ580-01 Drive, 160 kW, 293 A, Frame R8

MPN3ABD00046044-D
Active

ABB ACQ580-01 series, 3ABD00046044-D, wall-mounted LV AC drive, 160 kW normal-duty output, 293 A, frame size R8, IP21, NEMA Type 1 enclosure.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3ABD00046044-D specifications
ParameterValue
MountingWall-mounted
Enclosure type NEMAType1
Input voltage380 ... 500 V
Output current, normal use293 A
Output current, Heavy-Duty use246 A
Output current, Light-Overload use278 A
Output power, normal use160 kW
Output power, Heavy-Duty use132 kW
Output power, Light-Overload use160 kW
Frequency47.5 ... 63 Hz
Phases3-phase
IP ratingIP21
Frame sizeR8
Efficiency levelIE2

Product details

Drive selection memo for the ACQ580-01

The 3ABD00046044-D: Enclosure is IP21 with a NEMA Type 1 rating — splash-proof from the front, but not hose-down rated. Fine for indoor pump houses or treatment plants with controlled environments. Frame size R8 means it's a larger cabinet-mount unit; plan for wall-mount installation with adequate clearance for airflow.

Efficiency class is IE2, which is the baseline for standard industrial drives in most markets. Not premium efficiency, but appropriate for water/wastewater where pumps run at near-constant speed. The IP21 / NEMA 1 enclosure means it's not suitable for washdown areas or outdoor installation without additional weather protection.

Frequently asked questions

What is the frame size and enclosure rating?

Frame size R8, IP21 enclosure with NEMA Type 1 rating, wall-mounted installation.

What are the key output ratings for normal and heavy duty?

Normal use: 160 kW, 293 A. Heavy duty: 132 kW, 246 A. Light overload: 160 kW, 278 A.

What input voltage and frequency does this drive accept?

Three-phase input, 380 to 500 V, 47.5 to 63 Hz.

MPN
3ABD00046044-D