Frame R10, IP00 open type — cabinet-built module without enclosure, for panel integration.
Normal-use output is 355 kW / 650 A; heavy-duty rating is 250 kW / 477 A. Size against the heavy-duty figure for sustained overloads.
Installation notes
IP00 means no touch protection — mount inside a cabinet with appropriate clearance for airflow and arc flash. Frame R10 dictates the mounting footprint and bus-bar connections; verify gland-plate entry and cable bend radius before panel layout. The open-type NEMA rating confirms it's not standalone; it's a drive module that becomes part of a larger assembly.