Duty ratings in practice
The 3ABD00046113-D: The three duty columns cover the typical application range: normal-use 22 kW / 27 A for constant-torque loads like conveyors and pumps; heavy-duty 18.5 kW / 23 A for higher peak demands on crushers or extruders; light-overload 22 kW / 25.7 A for variable-torque fans and centrifugal pumps. The heavy-duty current is the one that governs thermal sizing in cyclic applications — if your load profile includes sustained overloads, size to the 23 A figure, not the 27 A normal rating.
Active lifecycle — the drive is current-production. No end-of-life notice on record. If you need a firm delivery date for a BOM freeze, send the RFQ with your target ship week.