The 3ABD00046128: Normal-use rating (Pn 5.5 kW, In 12.6 A) is the headline spec, but the heavy-duty curve matters if you're driving a pump or fan with a constant-torque profile. Heavy-duty use is rated at 4 kW and 9.4 A — that's the figure to size against for a positive-displacement pump or a conveyor. Light-overload use (5.5 kW, 12 A) mirrors the normal-use power but pulls slightly less current, which suggests a lower crest factor in the load profile. If your motor plate says 5.5 kW but your application cycles hard, check the heavy-duty column first.
Wall-mounted, frame R1. If this drive is going into a panel that sees hose spray or high humidity, you'd need a higher IP rating or a separate enclosure. The NEMA Type 1 rating confirms indoor use only.