The ABB 3ABD00046368 is a wall-mounted LV AC drive for HVAC duty. Rated 90 kW normal use at 169 A output current, with light-overload capability at the same 90 kW (161 A). Input accepts 380–480 V three-phase, 47.5–63 Hz. Frame size R7, IP20 enclosure, open type per NEMA. Standby loss sits at 36 W.
The 90 kW normal-use rating (Pn) matches the motor nameplate for continuous fan or pump loads. Light-overload (PlD) is also 90 kW, so the drive is sized for constant-torque HVAC profiles without extra headroom. The 169 A normal-use current (In) is the figure to check against the motor FLA; the 161 A light-overload current (IlD) applies when the drive runs below 40 °C ambient. IE2 efficiency keeps losses predictable for energy calculations.