ABB 3ABD00046393 — AC Drive (VFD) 480V

ABB 3ABD00046393 ACQ531-01 Drive, 132 kW, 246 A, Frame R8

MPN3ABD00046393
Active

ABB ACQ531-01-246A-4, Frame R8, 132 kW normal-use output, 246 A output current, 380-480 V 3-phase, IP20, IE2.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3ABD00046393 — Power & Output
ParameterValue
Output power, normal duty132 kW
Output current, normal duty246 A
Output power, light overload132 kW
Output current, light overload234 A
Apparent power output170.0 kV·A
Efficiency class (IE)IE2
Standby power loss47 W
3ABD00046393 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3ABD00046393 — Mechanical & Cooling
ParameterValue
Frame sizeR8
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule
3ABD00046393 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C

Product details

The ABB 3ABD00046393 is an ACQ531-01-246A-4 drive in Frame R8, rated for 132 kW normal-use output and 246 A output current on a 380-480 V three-phase supply. The 170.0 kV·A apparent power rating tells you the transformer or upstream feeder needs to support that full-load kVA, not just the 132 kW real power — a common miss on motor-drive sizing. Light-overload duty (234 A, 132 kW) matches the normal-use power, so this frame is sized for continuous rated load rather than short-duration overload headroom. Standby loss sits at 47 W — relevant for panel heat-budget calculations in a sealed enclosure. The drive is rated IE2 efficiency and accepts 47.5-63 Hz input, covering 50/60 Hz grids globally. Maximum ambient is 40 °C; the Open Type NEMA rating means it expects installation inside a clean, ventilated enclosure — not a standalone outdoor location.

Integration notes

Frame R8 is a module-style mounting — expect a floor-mount or back-panel footprint with bus-bar and cable entry points sized for the 246 A output. The 47 W standby loss is continuous whenever the DC bus is precharged, so factor it into the enclosure cooling calculation even when the motor is stopped.

Frequently asked questions

What is the frame size of 3ABD00046393?

The frame size is R8, which is the mechanical footprint for this drive rating. Frame R8 determines the mounting hole pattern, bus-bar spacing, and cable entry clearance.

What is the standby loss of this drive?

Standby loss is 47 W. This is the power dissipated when the drive is powered but the motor is not running — relevant for enclosure heat-load calculations.

Where can I buy 3ABD00046393?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial response.