Skip to main content
ABB 3ABD00046722-D — AC Drive (VFD) 480V

ABB 3ABD00046722-D ACS580-01-12A7-4+N7530 Drive, 5.5 kW, IP2

MPN3ABD00046722-D
Active

ABB ACS580-01 LV AC general-purpose wall-mounted drive, 3ABD00046722-D, 5.5 kW normal use, 12.6 A output, 380-480 V input, IP21, IE2, frame size R1.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Power & Output

3ABD00046722-D — Power & Output
ParameterValue
Output power, normal duty5.5 kW
Output current, normal duty12.6 A
Output power, heavy duty4.0 kW
Output current, heavy duty9.4 A
Output power, light overload5.5 kW
Output current, light overload12.0 A
Efficiency class (IE)IE2

Input / Supply

3ABD00046722-D — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Mechanical & Cooling

3ABD00046722-D — Mechanical & Cooling
ParameterValue
Frame sizeR1
NEMA enclosure typeType1
Degree of protection (IP)IP21
Mounting typeWall-mounted

Product details

This ABB ACS580-01 wall-mounted drive (order code 3ABD00046722-D) is sized for a 5.5 kW normal-duty motor on 380–480 V three-phase. The normal-use output current is 12.6 A; for heavy-duty applications like conveyors or pumps with constant torque, it delivers 4.0 kW at 9.4 A. Light-overload use (variable torque, fans) matches the 5.5 kW normal rating with a slightly lower 12.0 A current limit. The 47.5–63 Hz input frequency range covers 50 Hz and 60 Hz grids without adjustment.

The heavy-duty current (9.4 A at 4.0 kW) is the number to watch if you're driving a constant-torque load — a positive-displacement pump or a conveyor. The normal-use figure (12.6 A at 5.5 kW) applies to variable-torque fans and centrifugal pumps. Picking the wrong duty class means either nuisance tripping or leaving capacity on the table. The IP21 enclosure handles indoor, clean-ish environments; for washdown or dust, you'd need a higher IP rating. IE2 efficiency class is standard for this power band. If your site requires IE3 or IE4 for energy rebates or local codes, check the motor match — the drive itself doesn't enforce the motor efficiency class, but pairing an IE2 drive with an IE3 motor still meets the motor's performance curve.

Frequently asked questions

What is the frame size of 3ABD00046722-D?

Frame size R1. That's the smallest frame in the ACS580-01 line, suited for the 5.5 kW power class. Wall-mount compatible.

What input voltage and frequency does this drive accept?

Three-phase 380–480 V AC, 47.5–63 Hz. Covers 50 Hz and 60 Hz grids globally without adjustments.

What is the heavy-duty output rating?

Heavy-duty use (constant torque) is 4.0 kW at 9.4 A. Normal use (variable torque) is 5.5 kW at 12.6 A. Light-overload use matches normal power at 12.0 A.

MPN
3ABD00046722-D