Wall-mounted drive, order code 3ABD00046942-D, sized for 160 kW normal duty on 380-480 V three-phase. Output current sits at 293 A for normal use, 278 A under light-overload profile — both within the R8 frame's thermal capacity.
The 293 A normal-duty figure governs continuous motor current — size your line reactor and cables off that, not the light-overload 278 A. Light-overload rating (same 160 kW output, lower current) gives headroom for cyclic loads without oversizing the drive.