Skip to main content
ABB 3ABD00047992-D — AC Drive (VFD) 480V

3ABD00047992-D ACS580-01-073A-4+X1664, 37 kW, 73 A

MPN3ABD00047992-D
Active

ABB ACS580-01-073A-4+X1664, LV AC general-purpose wall-mounted drive, 37 kW normal use, 73 A output, 380-480 V 3-phase, IP21, NEMA 1, IE2, Frame R4.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Power & Output

3ABD00047992-D — Power & Output
ParameterValue
Output power, normal duty37 kW
Output current, normal duty73 A
Output power, heavy duty30.0 kW
Output current, heavy duty61 A
Output power, light overload37 kW
Output current, light overload68 A
Efficiency class (IE)IE2

Input / Supply

3ABD00047992-D — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Mechanical & Cooling

3ABD00047992-D — Mechanical & Cooling
ParameterValue
Frame sizeR4
NEMA enclosure typeType1
Degree of protection (IP)IP21
Mounting typeWall-mounted

Product details

The 3ABD00047992-D is an ABB ACS580-01-073A-4+X1664 LV AC general-purpose wall-mounted drive. It delivers 37 kW normal-use output at 73 A from a 380-480 V three-phase supply. Frame size R4, IP21 enclosure, NEMA Type 1. Efficiency class IE2. Frequency range 47.5-63 Hz.

Rating breakdown

The normal-use (Pn) rating of 37 kW at 73 A is the headline number, but the heavy-duty rating tells the real story for constant-torque loads: 30.0 kW at 61 A. Light-overload use (PlD) matches the normal-use kW at 68 A — useful for pumps and fans where the load profile is predictable.

WEEE Category 4 (Large Equipment) applies. The drive carries IP21 and NEMA Type 1 ratings. Efficiency is IE2. Standard documentation from ABB includes the product manual and compliance declarations for the relevant markets.

Frequently asked questions

What is the frame size and enclosure type?

Frame size R4, wall-mounted, IP21, NEMA Type 1. Suitable for indoor installation in clean environments.

What are the heavy-duty output ratings?

Heavy-duty use (PhD) is 30.0 kW at 61 A. This is the rating to use for constant-torque loads like conveyors or extruders.

MPN
3ABD00047992-D