Skip to main content
ABB 3ABD00048116 — AC Drive (VFD) 480V

ABB 3ABD00048116 ACS380 drive, 5.5 kW, 12.6 A, IP20

MPN3ABD00048116
Active

ABB ACS380-040C-12A6-4, 3ABD00048116, LV AC machinery drive, 5.5 kW normal use, 12.6 A, 380-480 V 3-phase, IP20, frame R2, IE2.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3ABD00048116 — Power & Output
ParameterValue
Output power, normal duty5.5 kW
Output current, normal duty12.6 A
Output power, heavy duty4 kW
Output current, heavy duty9.4 A
Output power, light overload5.5 kW
Output current, light overload12 A
Efficiency class (IE)IE2
3ABD00048116 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3ABD00048116 — Mechanical & Cooling
ParameterValue
Frame sizeR2
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule

Product details

The ABB 3ABD00048116 is an ACS380-040C-12A6-4 LV AC machinery drive module, rated 5.5 kW normal-use output at 12.6 A, with a heavy-duty rating of 4 kW at 9.4 A. It runs on 380-480 V three-phase input, 47.5-63 Hz, and sits in a frame size R2 enclosure with IP20 protection. Efficiency class is IE2.

The 12.6 A normal-use current (Pn 5.5 kW) is the number to match against your motor's full-load amps for continuous duty. The heavy-duty curve (9.4 A, 4 kW) covers applications with higher starting torque or cyclic overloads — conveyors, crushers, that sort of thing. Both ratings are at the drive's output, so factor in cable losses if the run is long. The IP20 enclosure means it's for indoor panel mounting, not washdown zones.

Integration notes

Frame R2 is a compact size — fits in a standard 400 mm wide cabinet without crowding. Three-phase input at 380-480 V covers most European and North American line voltages; the 47.5-63 Hz input range handles both 50 Hz and 60 Hz mains. No special cooling duct required at this rating, but keep the ambient below 40 °C for full current capability.

Frequently asked questions

What is the frame size of this drive?

Frame size R2. That's the mechanical footprint for panel layout and mounting hole pattern.

What efficiency class is this drive?

IE2. That's standard for this generation of machinery drives — meets the base regulatory requirement for most industrial applications.

MPN
3ABD00048116