The ABB 3ABD00048146 is an ACS380-040C-25A0-4 LV AC machinery drive module, frame size R3, rated for 11 kW normal-use output at 25 A on a 380-480 V three-phase supply. Heavy-duty rating is 7.5 kW / 17 A, light-overload rating 11 kW / 23.8 A. Efficiency class IE2, protection IP20, open type enclosure. Frequency range 47.5-63 Hz.
The 25 A normal-use current (In) at 11 kW is the headline number for sizing a standard constant-torque load. If the application cycles hard or runs a high-inertia load, the heavy-duty curve at 17 A / 7.5 kW is the rating that governs thermal capacity — that is the figure to check against motor FLA plus service factor. Light-overload use at 23.8 A / 11 kW covers most pump and fan profiles. Frame R3 determines the mounting footprint and the gland-plate layout. IP20 means the drive is intended for enclosure mounting — no washdown, no dust ingress protection. Open-type NEMA enclosure confirms it is not a standalone unit.