It runs on a 380-480 V three-phase supply, 47.5-63 Hz, and comes in frame size R10 with an IP00 open-type enclosure.
This module carries three distinct output ratings. Normal use (Pn) delivers 250 kW at 505 A — that's the continuous rating for typical pump/fan loads. Heavy-duty use (PhD) drops to 200 kW at 361 A, sized for constant-torque applications like conveyors or extruders. Light-overload use (PlD) matches the normal power at 250 kW but at a slightly lower 485 A, reflecting a different duty cycle profile.
Physical and installation notes
Frame size R10 is a module-style construction — no enclosure, IP00, open type. Efficiency class IE2 is the baseline for this generation; it meets the minimum standard for most industrial applications in regions where IE2 is still accepted for variable-speed drives.