ABB ACS580-01 132 kW Drive, 3ABD00048297-D, 246 A

MPN3ABD00048297-D
Active

ABB ACS580-01 series, LV AC general purpose wall-mounted drive, 3ABD00048297-D, 132 kW / 246 A normal duty, 380-500 VAC input.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical

3ABD00048297-D — Electrical
ParameterValue
Input voltage380 ... 500 V
Frequency47.5 ... 63 Hz
Number of phases3-phase

Power & Current

3ABD00048297-D — Power & Current
ParameterValue
Output power, normal duty132 kW
Output power, heavy duty110 kW
Output power, light-overload duty132 kW
Output current, heavy duty206 A
Output current, normal duty246 A
Output current, light-overload duty234 A
Efficiency class (IE)IE2

Protection & Environmental

3ABD00048297-D — Protection & Environmental
ParameterValue
Degree of protection (IP)IP21
NEMA enclosure typeType1

Mechanical

3ABD00048297-D — Mechanical
ParameterValue
Frame sizeR8
Mounting typeWall-mounted

Product details

The 3ABD00048297-D: Normal-use rating sits at 132 kW / 246 A — that's the continuous capability for typical variable-torque loads like fans and pumps. Heavy-duty use drops to 110 kW / 206 A, which is the headroom for constant-torque applications such as conveyors or extruders where you need sustained torque at low speed. Light-overload use is spec'd at 132 kW / 234 A, slightly below the normal-use current because the overload profile differs.

R8 frame size, wall-mounted. IP21 and NEMA Type 1 mean it's suited for indoor, clean environments — no washdown, no dust. The wall-mount form factor saves floor space but plan for the R8 footprint when laying out the panel; it's a substantial drive at this power level.

Frequently asked questions

What is the frame size of the 3ABD00048297-D?

The frame size is R8.

What are the key power ratings for this drive?

Normal duty: 132 kW / 246 A. Heavy duty: 110 kW / 206 A. Light overload: 132 kW / 234 A. Input is 380-500 V three-phase at 47.5-63 Hz.

What is the enclosure type and protection rating?

IP21 degree of protection with a NEMA Type 1 enclosure, suitable for indoor, clean environments.