Skip to main content
ABB 3ABD00048308-D — AC Drives (VFD)

ABB 3ABD00048308-D ACS580-01-018A-4+P974 Drive, 7.5 kW, 17 A

MPN3ABD00048308-D
Active

ABB ACS580-01-018A-4+P974, general-purpose wall-mounted drive, 7.5 kW normal use, 17 A output, 380–500 V, IP21, Type 1 enclosure.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical

3ABD00048308-D — Electrical
ParameterValue
Input voltage380 ... 500 V
Frequency47.5 ... 63 Hz
Number of phases3-phase

Power & Current

3ABD00048308-D — Power & Current
ParameterValue
Output power, normal duty7.5 kW
Output power, heavy duty5.5 kW
Output power, light-overload duty7.5 kW
Output current, heavy duty12.6 A
Output current, normal duty17 A
Output current, light-overload duty16.2 A
Efficiency class (IE)IE2

Protection & Environmental

3ABD00048308-D — Protection & Environmental
ParameterValue
Degree of protection (IP)IP21
NEMA enclosure typeType1

Mechanical

3ABD00048308-D — Mechanical
ParameterValue
Frame sizeR2
Mounting typeWall-mounted

Product details

The ABB 3ABD00048308-D is the order code for a general-purpose wall-mounted drive, rated 7.5 kW normal-use output at 17 A, with heavy-duty capability of 5.5 kW at 12.6 A. It runs on three-phase 380–500 V input, 47.5–63 Hz, and carries an IE2 efficiency level.

Ratings in Practice

The normal-use rating (7.5 kW, 17 A) is the continuous motor rating for a standard 4-pole induction motor on 400 V. The heavy-duty curve (5.5 kW, 12.6 A) applies when the load profile includes sustained overload — pumps with high starting torque or conveyors with breakaway loads. Light-overload use is rated at the same 7.5 kW but with a slightly lower current of 16.2 A, which may suit constant-torque applications where the drive is sized to the motor nameplate rather than the peak demand.

Wall-mounted, IP21, NEMA Type 1 — suitable for indoor, dry locations with no falling dirt or dripping water. Frame size R2 keeps the footprint compact for a 7.5 kW drive; plan for clearance above and below for airflow. The 47.5–63 Hz input range covers 50 Hz and 60 Hz grids without derating.

Frequently asked questions

What is the frame size of this drive?

Frame size R2.

What compliance documentation is available for this drive?

The drive carries a WEEE Category 5 classification (small equipment under 50 cm). Standard ABB documentation includes the product manual, EC Declaration of Conformity, and installation instructions — request these with your RFQ.

MPN
3ABD00048308-D