ABB 3ABD00048322-D — Inverter / VFD

ABB 3ABD00048322-D ACS580-01 Wall-Mount Drive, 200 kW, 363 A

MPN3ABD00048322-D
Active

ABB ACS580-01 general-purpose wall-mounted drive, 3ABD00048322-D, 200 kW normal-use output, 363 A, 380–500 V 3-phase, frame size R9, IP21, IE2.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3ABD00048322-D specifications
ParameterValue
MountingWall-mounted
Enclosure type NEMAType1
Input voltage380 ... 500 V
Output current, normal use363 A
Output current, Heavy-Duty use293 A
Output current, Light-Overload use345 A
Output power, normal use200 kW
Output power, Heavy-Duty use160 kW
Output power, Light-Overload use200 kW
Frequency47.5 ... 63 Hz
Phases3-phase
IP ratingIP21
Frame sizeR9
Efficiency levelIE2

Product details

The ABB 3ABD00048322-D is an ACS580-01 wall-mounted general-purpose drive rated for 200 kW normal use at 363 A output, with heavy-duty capability of 160 kW at 293 A. It runs on 380–500 V three-phase input, 47.5–63 Hz, so it handles 50 Hz and 60 Hz mains without a line reactor swap. Frame size R9 and IP21 / NEMA Type 1 enclosure mean it goes on a wall indoors — no extra shelter needed, but keep it out of washdown zones.

The two current ratings matter differently. Normal-use 363 A (200 kW) is your continuous motor load at rated speed. Heavy-duty 293 A (160 kW) is what the drive can deliver for constant-torque or high-start-torque applications — conveyors, crushers, extruders. If your motor plate says 200 kW but the load is a screw feeder that starts loaded, size against the 293 A heavy-duty figure, not the headline 363 A. Light-overload rating 345 A (200 kW) sits between them, covering pumps and fans with moderate starting torque.

Wall-mounted, frame R9. IP21 keeps out fingers and falling dust — fine for a clean electrical room, not for outdoor or wet areas. NEMA Type 1 equivalent. No DIN-rail option at this frame; it bolts to a backplate. Plan for cable entry from the bottom or side through the gland plate. The drive is large equipment per WEEE Category 4, so factor end-of-life recycling into your compliance paperwork.

Frequently asked questions

What is the frame size and what does it mean for installation?

Frame size R9. This is a wall-mounted drive requiring a backplate — no DIN-rail mount at this size. The IP21 / NEMA Type 1 enclosure is for indoor use only.

How do the normal-use and heavy-duty ratings compare?

Normal-use output is 200 kW at 363 A. Heavy-duty output is 160 kW at 293 A. For constant-torque loads like conveyors or extruders, size against the heavy-duty current rating, not the normal-use figure.