Skip to main content
ABB 3ABD00048402-D — AC Drive (VFD) 480V

ABB 3ABD00048402-D ACS580-01 Drive, 5.5 kW, 12.6 A, Frame R1

MPN3ABD00048402-D
Active

ABB ACS580-01, LV AC general purpose wall-mounted drive, Frame R1, 380-480 V, 3-phase, 5.5 kW / 12.6 A normal use, IP21, IE2.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Power & Output

3ABD00048402-D — Power & Output
ParameterValue
Output power, normal duty5.5 kW
Output current, normal duty12.6 A
Output power, heavy duty4.0 kW
Output current, heavy duty9.4 A
Output power, light overload5.5 kW
Output current, light overload12.0 A
Efficiency class (IE)IE2

Input / Supply

3ABD00048402-D — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Mechanical & Cooling

3ABD00048402-D — Mechanical & Cooling
ParameterValue
Frame sizeR1
NEMA enclosure typeType1
Degree of protection (IP)IP21
Mounting typeWall-mounted

Product details

Drive selection note — 5.5 kW normal duty, Frame R1

The ABB 3ABD00048402-D is an ACS580-01 wall-mounted drive rated 5.5 kW normal-use output at 12.6 A, with a heavy-duty rating of 4.0 kW / 9.4 A for constant-torque loads like conveyors or positive-displacement pumps. Input accepts 380-480 V three-phase, 47.5-63 Hz.

Duty ratings — match the load profile

Normal-use (light overload) delivers 5.5 kW / 12.6 A; heavy-duty drops to 4.0 kW / 9.4 A. That 1.5 kW gap is the margin for starting torque and sustained overload on a crusher or extruder.

Lifecycle and sourcing — active, production current

Listed as current lifecycle stage and active in production.

Wall-mounted, NEMA Type 1 enclosure, IP21 protection. Suitable for indoor, non-condensing environments. Frame R1 dimensions keep the drive within standard panel depth.

Frequently asked questions

What is the frame size of 3ABD00048402-D?

Frame R1.

What input voltage and frequency does this drive accept?

380-480 V three-phase, 47.5-63 Hz.

What are the normal-use and heavy-duty power ratings?

Normal use: 5.5 kW / 12.6 A. Heavy duty: 4.0 kW / 9.4 A.

MPN
3ABD00048402-D