The 3ABD00048854-D: The 5.5 kW normal-use (Pn) rating at 12.6 A is the headline spec for constant-torque applications like conveyors or fans. The heavy-duty (PhD) rating of 4 kW at 9.4 A applies for higher starting torque or cyclic loads — use that for sizing on pumps or compressors with variable load profiles. Light-overload (PlD) mirrors the normal-use power at 5.5 kW but with a slightly lower current of 12 A, which may suit variable-torque loads where peak demand is brief. The IE2 efficiency class means this drive meets the minimum efficiency standard for most industrial installations in regions that mandate motor-drive system efficiency. IP21 and NEMA Type 1 enclosure is suitable for clean, dry indoor environments — no washdown or dust rating, so keep it out of wet or dusty areas.
ABB 3ABD00048854-D ACS580-01 Drive, 5.5 kW, 12.6 A
MPN3ABD00048854-D
Active
ABB, ACS580-01 series, general-purpose wall-mounted drive, 3ABD00048854-D, 5.5 kW / 12.6 A normal use, 380-500 V, IP21, IE2, frame R1.
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →Specifications
Electrical
| Parameter | Value |
|---|---|
| Input voltage | 380 ... 500 V |
| Frequency | 47.5 ... 63 Hz |
| Number of phases | 3-phase |
Power & Current
| Parameter | Value |
|---|---|
| Output power, normal duty | 5.5 kW |
| Output power, heavy duty | 4 kW |
| Output power, light-overload duty | 5.5 kW |
| Output current, heavy duty | 9.4 A |
| Output current, normal duty | 12.6 A |
| Output current, light-overload duty | 12 A |
| Efficiency class (IE) | IE2 |
Protection & Environmental
| Parameter | Value |
|---|---|
| Degree of protection (IP) | IP21 |
| NEMA enclosure type | Type1 |
Mechanical
| Parameter | Value |
|---|---|
| Frame size | R1 |
| Mounting type | Wall-mounted |
Product details
Frequently asked questions
What is the frame size of 3ABD00048854-D?
Frame size R1.
What is the input voltage and frequency range?
380-500 V three-phase, 47.5-63 Hz.
What are the normal-use and heavy-duty output ratings?
Normal-use: 5.5 kW at 12.6 A. Heavy-duty: 4 kW at 9.4 A.
What enclosure protection does this drive have?
IP21 and NEMA Type 1, suitable for indoor, dry environments.
MPN
3ABD00048854-D