Wiring practice note
Frame B2 accepts standard motor and mains cable terminations for the 17 A rating. The DC-link terminals are accessible for an external braking resistor if the load profile demands rapid deceleration or vertical holding. Mount the drive on a flat metal backplate for thermal conduction; the heatsink is sized for the 7.5 kW continuous output at 40 °C ambient.