Skip to main content
ABB 3ABD00050170-D — AC Drives (VFD)

ABB 3ABD00050170-D ACS580-04 Drive Module, 355 kW, 650 A

MPN3ABD00050170-D
Active

ABB ACS580-04 drive module, 3ABD00050170-D, 355 kW / 650 A normal use, 380-500 V, 3-phase, IP00, frame R10, IE2.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical

3ABD00050170-D — Electrical
ParameterValue
Input voltage380 ... 500 V
Frequency47.5 ... 63 Hz
Number of phases3-phase

Power & Current

3ABD00050170-D — Power & Current
ParameterValue
Output power, normal duty355 kW
Output power, heavy duty250 kW
Output power, light-overload duty355 kW
Output current, heavy duty477 A
Output current, normal duty650 A
Output current, light-overload duty634 A
Efficiency class (IE)IE2

Protection & Environmental

3ABD00050170-D — Protection & Environmental
ParameterValue
Degree of protection (IP)IP00
NEMA enclosure typeOpen Type

Mechanical

3ABD00050170-D — Mechanical
ParameterValue
Frame sizeR10
Mounting typeModule

Product details

The ABB 3ABD00050170-D is an ACS580-04 general-purpose LV AC drive module rated for 355 kW normal-use output at 650 A, with a heavy-duty capability of 250 kW at 477 A. It runs on 380-500 V three-phase input, 47.5-63 Hz, and is built in frame size R10 as an open-type (IP00) module for cabinet integration.

Normal-use (light-overload) output is 355 kW / 634 A; heavy-duty drops to 250 kW / 477 A. IE2 efficiency is baseline for this class; no premium-efficiency premium here. IP00 open type means it lands in a panel, not on a wall. Frame R10 is a large chassis — plan for a 355 kW cabinet with busbar work and forced-air cooling.

Frequently asked questions

What is the frame size of 3ABD00050170-D?

Frame size R10. That is a large module — expect a substantial cabinet footprint and busbar connections.

What are the key output ratings?

Normal-use output is 355 kW at 650 A; heavy-duty output is 250 kW at 477 A. Light-overload rating matches normal use at 355 kW / 634 A.

What input voltage and frequency does it accept?

Three-phase 380-500 V AC, 47.5-63 Hz.

MPN
3ABD00050170-D