The 3ABD00050196-D: Normal-use output current is 820 A at 450 kW; heavy-duty use drops to 625 A at 355 kW. That 195 A delta between normal and heavy-duty tells you the thermal headroom — if your motor cycles hard or runs in a hot cabinet, you size off the 625 A heavy-duty number, not the 820 A headline. Light-overload use sits at 810 A, essentially matching normal use, so the drive is built for constant-torque applications, not a short-time overload machine.
This part carries an active lifecycle status — no phase-out, no NRND flag. That means you can freeze the BOM line without a PCN watch. WEEE category 4 (large equipment) applies for end-of-life disposal planning.
Frame R11 is a module-style mount, not a standalone cabinet; plan for gland-plate clearance and bus-bar connections at this current level. IE2 efficiency class meets the baseline for variable-torque loads.