Skip to main content
ABB 3ABD00050202-D — AC Drives (VFD)

ABB 3ABD00050202-D ACS580-04 Drive Module, 450 kW, 820 A

MPN3ABD00050202-D
Active

ABB ACS580-04 general purpose drive module, 3ABD00050202-D, 450 kW / 820 A normal use, 380-500 V three-phase, IP00, frame R11.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical

3ABD00050202-D — Electrical
ParameterValue
Input voltage380 ... 500 V
Frequency47.5 ... 63 Hz
Number of phases3-phase

Power & Current

3ABD00050202-D — Power & Current
ParameterValue
Output power, normal duty450 kW
Output power, heavy duty355 kW
Output power, light-overload duty450 kW
Output current, heavy duty625 A
Output current, normal duty820 A
Output current, light-overload duty810 A
Efficiency class (IE)IE2

Protection & Environmental

3ABD00050202-D — Protection & Environmental
ParameterValue
Degree of protection (IP)IP00
NEMA enclosure typeOpen Type

Mechanical

3ABD00050202-D — Mechanical
ParameterValue
Frame sizeR11
Mounting typeModule

Product details

Drive module for 450 kW motor loads

The ABB 3ABD00050202-D is an ACS580-04 LV AC general purpose drive module rated for 450 kW normal-use output at 820 A, with heavy-duty capability at 355 kW / 625 A. It accepts 380-500 V three-phase input over a 47.5-63 Hz range, making it a direct fit for 50/60 Hz industrial mains. The IP00 open-type enclosure means it's intended for cabinet mounting, not standalone floor placement.

Three duty ratings are listed: normal-use (450 kW / 820 A), light-overload (450 kW / 810 A), and heavy-duty (355 kW / 625 A). The heavy-duty current of 625 A is the figure to check for constant-torque applications like conveyors or extruders, where the drive must sustain higher peak loads without tripping.

Frame size R11 and IP00 protection mean the module is designed for cabinet integration with forced-air cooling. The open-type NEMA enclosure requires the installer to provide adequate clearance for airflow and maintain a clean, dry environment. WEEE category 4 applies for end-of-life recycling.

Frequently asked questions

What is 3ABD00050202-D's listed frame size?

The frame size is R11.

What is the input voltage and frequency range?

Input voltage is 380-500 V three-phase, 47.5-63 Hz.

What are the normal-use and heavy-duty output ratings?

Normal-use: 450 kW, 820 A. Heavy-duty: 355 kW, 625 A.

MPN