ABB 3ABD00050303-D — AC Drive (VFD) 480V

ABB 3ABD00050303-D ACS530 Drive, 315 kW, 585 A, Frame R10

MPN3ABD00050303-D
Active

ABB ACS530 series, AC drive, 3ABD00050303-D, 315 kW output, 585 A normal use, 380-480 V 3-phase, Frame R10, IP00, IE2.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3ABD00050303-D — Power & Output
ParameterValue
Output power, normal duty315 kW
Output current, normal duty585 A
Output power, light overload315 kW
Output current, light overload575 A
Apparent power output405 kV·A
Efficiency class (IE)IE2
Standby power loss396 W
3ABD00050303-D — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3ABD00050303-D — Mechanical & Cooling
ParameterValue
Frame sizeR10
NEMA enclosure typeOpen Type
Degree of protection (IP)IP00
Mounting typeCabinet-built
3ABD00050303-D — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C

Product details

The ABB 3ABD00050303-D is an ACS530-04-585A-4 drive delivering 315 kW output at 585 A normal use, with a light-overload rating of 575 A at the same power. It runs on 380-480 V three-phase, 47.5-63 Hz, and is built as a cabinet-mounted unit (no enclosure) with IP00 protection and NEMA Open Type construction. The frame size is R10, and standby loss sits at 396 W.

The 585 A normal-use current (In) and 575 A light-overload current (IlD) are the numbers that decide the cable sizing and upstream protection for this drive. Both share the same 315 kW power output, so the overload margin is slim — the light-overload rating is essentially the same as normal use, meaning this drive is sized for continuous duty at its nameplate. The 405 kVA apparent power output confirms the transformer or line reactor needs to handle that throughput. Ambient temperature is capped at 40 °C; above that, derating applies. The IP00 open type means it goes into a panel or cabinet — no standalone weatherproofing.

Frequently asked questions

What is the frame size of 3ABD00050303-D?

The frame size is R10, which determines the physical mounting footprint and cabinet cutout dimensions for this drive.

What is the standby loss for this drive?

Standby loss is 396 W. This is the heat dissipated when the drive is powered but not running a motor — relevant for cabinet cooling and ventilation sizing.

What compliance documentation is available for this drive?

The drive carries WEEE Category 5 classification (Small Equipment). For RoHS, REACH, and UL documentation, these are standard for ABB ACS530 drives and can be provided with the order upon request.

MPN
3ABD00050303-D