Skip to main content
ABB 3ABD00050553 — AC Drive (VFD) 480V

ABB 3ABD00050553 ACS380 Drive Module, 22 kW, 45 A, R4

MPN3ABD00050553
Active

ABB ACS380-040C-045A-4 low-voltage AC machinery drive module, 22 kW / 45 A normal duty, 380-480 V 3-phase, frame size R4, IP20, IE2.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3ABD00050553 — Power & Output
ParameterValue
Output power, normal duty22 kW
Output current, normal duty45 A
Output power, heavy duty18.5 kW
Output current, heavy duty38 A
Output power, light overload22 kW
Output current, light overload42.8 A
Efficiency class (IE)IE2
3ABD00050553 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3ABD00050553 — Mechanical & Cooling
ParameterValue
Frame sizeR4
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule

Product details

The ABB 3ABD00050553 is a low-voltage AC machinery drive module, rated 22 kW normal-use output at 45 A from a 380-480 V three-phase supply. It carries a heavy-duty rating of 18.5 kW at 38 A for constant-torque loads.

Normal-use output of 45 A (22 kW) is the figure for standard variable-torque applications like fans and pumps. The heavy-duty curve drops to 38 A (18.5 kW) — that is the rating to size against for constant-torque loads such as conveyors or positive-displacement pumps. A light-overload rating of 42.8 A (22 kW) sits between them, covering applications with occasional overload cycles. Pick the duty class that matches your load profile; the heavy-duty number is the conservative one for a motor that must hold torque through a stall condition.

Input and frame considerations

Input accepts 380-480 VAC three-phase, 47.5-63 Hz. Frame size R4 determines panel cutout and mounting hole pattern.

Frequently asked questions

What are the normal-duty and heavy-duty ratings?

Normal-use output is 22 kW at 45 A. Heavy-duty output is 18.5 kW at 38 A. A light-overload rating of 22 kW at 42.8 A is also listed.

What is the frame size of this drive?

Frame size is R4.

What input voltage and frequency does it accept?

Input is 380-480 VAC three-phase, 47.5-63 Hz.

What is the enclosure protection rating?

IP20, open type — suitable for cabinet mounting in a clean environment.

MPN