ABB 3ABD00050625 — AC Drive (VFD) 480V

ABB 3ABD00050625 ACS380 Drive, 0.55 kW / 1.8 A, Frame R0

MPN3ABD00050625
Active

ABB ACS380-040C-01A8-4+K490 drive module, 0.55 kW / 1.8 A, 380–480 V three-phase, Frame R0, IP20, IE2.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3ABD00050625 — Power & Output
ParameterValue
Output power, normal duty0.55 kW
Output current, normal duty1.8 A
Output power, heavy duty0.37 kW
Output current, heavy duty1.2 A
Output power, light overload0.55 kW
Output current, light overload1.7 A
Efficiency class (IE)IE2
3ABD00050625 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3ABD00050625 — Mechanical & Cooling
ParameterValue
Frame sizeR0
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule

Product details

Drive selection memo — 0.55 kW class

The ABB 3ABD00050625 is a drive module sized for a 0.55 kW motor on 380–480 V three-phase mains. Normal-duty output is 1.8 A; heavy-duty output is 0.37 kW at 1.2 A. Frame size R0 fits tight panel layouts. IP20 enclosure means it's intended for inside a cabinet.

The 1.8 A normal-duty current (1.7 A light-overload) drives a standard 0.55 kW induction motor on a pump or fan curve. If the load is constant-torque — a small conveyor, extruder, or positive-displacement pump — the heavy-duty rating of 1.2 A at 0.37 kW is the governing figure. The 380–480 V input covers 400 V and 480 V grids worldwide; the 47.5–63 Hz frequency range handles both 50 Hz and 60 Hz supplies without derating. IE2 efficiency meets the EU Ecodesign directive minimum for this power band.

Standard supply through ABB's distribution channel; no need to stockpile.

Frequently asked questions

What is the frame size of this drive?

Frame size R0 — the smallest frame in the ACS380 family, designed for compact panel mounting.

What are the key output ratings for normal and heavy duty?

Normal-duty output is 0.55 kW at 1.8 A. Heavy-duty (constant-torque) output is 0.37 kW at 1.2 A. Light-overload rating is 0.55 kW at 1.7 A.

MPN
3ABD00050625