ABB 3ABD00050628 — AC Drive (VFD) 480V

ABB 3ABD00050628 ACS380 Drive Module, 1.5 kW, 4 A

MPN3ABD00050628
Active

ABB ACS380 drive module, 3ABD00050628, 380-480 V 3-phase, 1.5 kW / 4 A normal duty, IP20, IE2, Frame R1.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3ABD00050628 — Power & Output
ParameterValue
Output power, normal duty1.5 kW
Output current, normal duty4 A
Output power, heavy duty1.1 kW
Output current, heavy duty3.3 A
Output power, light overload1.5 kW
Output current, light overload3.8 A
Efficiency class (IE)IE2
3ABD00050628 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3ABD00050628 — Mechanical & Cooling
ParameterValue
Frame sizeR1
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule

Product details

The ABB 3ABD00050628 is a low-voltage AC machinery drive module from the ACS380 family, rated for 1.5 kW normal-use output at 4 A on a 380-480 V three-phase supply. It's sized for a 3-phase induction motor, and the heavy-duty rating drops to 1.1 kW and 3.3 A for constant-torque loads like conveyors or positive-displacement pumps. The frame is R1, which tells you the mechanical footprint and heatsink capacity — it's the smallest frame in the ACS380 line, meant for panel mounting where space is tight.

The normal-use current of 4 A (light-overload 3.8 A) is the number you size the motor branch circuit for — match it to a motor nameplate full-load current at or below that figure. The heavy-duty current of 3.3 A covers applications where the drive runs at rated torque continuously, like a crusher or mixer. Input frequency is 47.5 to 63 Hz, so it handles 50 Hz and 60 Hz grids without derating. The IE2 efficiency level means it meets the minimum efficiency standard for variable-speed drives in most regions — nothing special, but compliant for general industrial use.

IP20 enclosure, so it's for clean, dry indoor panels only — no washdown or dusty environments without a separate enclosure. The open-type NEMA rating (no NEMA 1/12 enclosure) confirms it's meant for installation inside a larger cabinet. Frame R1 dictates the DIN-rail or screw-mount hole pattern; check the mechanical drawing for the exact footprint before cutting the backplate.

Frequently asked questions

What is the frame size of this module?

Frame R1 — the smallest frame in the ACS380 family, designed for compact panel mounting.

What are the normal-use and heavy-duty output ratings?

Normal use: 1.5 kW at 4 A. Heavy-duty: 1.1 kW at 3.3 A. Light-overload: 1.5 kW at 3.8 A.