ABB 3ABD00057902 — AC Drive (VFD) 480V

ABB 3ABD00057902 ACS380 Drive Module, 22 kW / 45 A, R4

MPN3ABD00057902
Active

ABB ACS380 series, machinery drive module, 3ABD00057902, 22 kW normal-use / 18.5 kW heavy-duty, 45.0 A / 38.0 A, 380-480 V 3-phase, IP20, R4 frame.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3ABD00057902 — Power & Output
ParameterValue
Output power, normal duty22 kW
Output current, normal duty45.0 A
Output power, heavy duty18.5 kW
Output current, heavy duty38.0 A
Output power, light overload22.0 kW
Output current, light overload42.8 A
Efficiency class (IE)IE2
3ABD00057902 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3ABD00057902 — Mechanical & Cooling
ParameterValue
Frame sizeR4
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule

Product details

The ABB 3ABD00057902 is an ACS380-series machinery drive module rated for 22 kW normal-use output at 45.0 A on a 380–480 V three-phase supply. Heavy-duty cycle drops to 18.5 kW / 38.0 A — that 38 A figure is the one to size branch protection against if the load profile includes shock starts or constant torque below base speed.

Frame size R4 tells you the mechanical envelope and the bus-bar layout — it is the same footprint as other R4 ACS380 variants, so a panel cutout or gland plate designed for one R4 module accepts this one. The IP20 enclosure means it is panel-mount only; no conduit entries on the drive itself, so plan for a separate enclosure if the environment is dusty or wet. Efficiency is IE2, which is the baseline for this power class under IEC 61800-9-2. If your project requires IE3 or IE4 for energy-code compliance, this module meets the minimum, not the premium tier. Input frequency acceptance spans 47.5 to 63 Hz, so it handles 50 Hz and 60 Hz grids without derating — common for export panels or sites with generator backup that drifts off-nominal.

Frequently asked questions

What is the frame size of 3ABD00057902?

Frame size R4. That determines the mounting hole pattern, bus-bar spacing, and overall dimensions for panel layout.

What compliance documentation is available for this drive?

The drive carries an IEC efficiency rating of IE2. For specific declarations (CE, UKCA, RoHS, REACH, UL), request the manufacturer's Declaration of Conformity or the product compliance sheet from your ABB channel partner.

MPN